Transient response to three-phase faults on a wind turbine generatorIn order to obtain a measure of its responses to short circuits a large horizontal axis wind turbine generator was modeled and its performance was simulated on a digital computer. Simulation of short circuit faults on the synchronous alternator of a wind turbine generator, without resort to the classical assumptions generally made for that analysis, indicates that maximum clearing times for the system tied to an infinite bus are longer than the typical clearing times for equivalent capacity conventional machines. Also, maximum clearing times are independent of tower shadow and wind shear. Variation of circuit conditions produce the modifications in the transient response predicted by analysis.
Document ID
19780018599
Acquisition Source
Legacy CDMS
Document Type
Thesis/Dissertation
Authors
Gilbert, L. J.
(NASA Lewis Research Center Cleveland, OH, United States)
Date Acquired
September 3, 2013
Publication Date
June 1, 1978
Subject Category
Energy Production And Conversion
Report/Patent Number
E-9638
NASA-TM-78902
Report Number: E-9638
Report Number: NASA-TM-78902
Accession Number
78N26542
Distribution Limits
Public
Copyright
Work of the US Gov. Public Use Permitted.