Measured performance of a 3-ton LiBr absorption water chiller and its effect on cooling system operationA 3-ton lithium bromide absorption water chiller was tested for a number of conditions involving hot-water input, chilled water, and the cooling water. The primary influences on chiller capacity were the hot water inlet temperature and the cooling water inlet temperature. One combination of these two parameters extended the output to as much as 125% of design capacity, but no combination could lower the capacity to below 60% of design. A cooling system was conceptually designed so that it could provide several modes of operation. Such flexibility is needed for any solar cooling system to be able to accommodate the varying solar energy collection and the varying building demand. It is concluded that a 3-ton absorption water chiller with the kind of performance that was measured can be incorporated into a cooling system such as that proposed, to provide efficient cooling over the specified ranges of operating conditions.
Document ID
19770066313
Acquisition Source
Legacy CDMS
Document Type
Conference Paper
Authors
Namkoong, D.
(NASA Lewis Research Center Cleveland, Ohio, United States)
Date Acquired
August 9, 2013
Publication Date
August 1, 1976
Subject Category
Energy Production And Conversion
Meeting Information
Meeting: Joint Conference on Sharing the Sun: Solar Technology in the Seventies
Location: Winnipeg
Country: Canada
Start Date: August 15, 1976
End Date: August 20, 1976
Sponsors: International Solar Energy Society, Solar Energy Society of Canada
Accession Number
77A49165
Distribution Limits
Public
Copyright
Other

Available Downloads

There are no available downloads for this record.
No Preview Available