NASA Logo

NTRS

NTRS - NASA Technical Reports Server

Press Enter or click the Search button to begin your search.

Back to Results
Electrical enclosure hydrogen intrusion studyAs a cost savings measure for the space shuttle program, the feasibility of substituting dry air for nitrogen as the purge gas used to minimize the probability of fire and explosions which could erupt from propellant vapor (hydrogen) diffusion into the electrical enclosures at Launch Complex 39 was investigated. It was concluded that: (1) Hydrogen concentrations of approximately 1% were obtained in an electrical enclosure under design purge conditions. (2) Hydrogen concentrations exceeding the lower explosive limit, 4%, could probably be obtained within the enclosure under worst case conditions. (3) Most of the hydrogen intrusion into the enclosure probably occurred at the point with the shortest leak path, such as the door seal. (4) More stringent electrical enclosure design requirements should be imposed before air is using as a purge gas.
Document ID
19790017690
Acquisition Source
Legacy CDMS
Document Type
Technical Publication (TP)
Authors
Welch, P. J.
(NASA John F. Kennedy Space Center Cocoa Beach, FL, United States)
Yantsios, J. N.
(NASA John F. Kennedy Space Center Cocoa Beach, FL, United States)
Date Acquired
September 3, 2013
Publication Date
June 1, 1979
Subject Category
Atomic And Molecular Physics
Report/Patent Number
NASA-TP-1461
KSC-TR-72-1
Report Number: NASA-TP-1461
Report Number: KSC-TR-72-1
Accession Number
79N25861
Distribution Limits
Public
Copyright
Work of the US Gov. Public Use Permitted.
No Preview Available